Writer: admin Time:2020-05-27 00:00:00 Browse:1065℃
Comparison project | Original shell and tube type cold dryer | Energy-saving plate type cold dryer |
Volume flow | 85Nm³/min | 85Nm³/min |
Pressure drop | The new machine is 0.55bar, 1.2bar half a year later, and 1.7bar two years later. The inside and outside of the pipeline are rusted, and the user is scrapped for reconstruction | 0.23bar (including filter), still 0.25bar after 7 months |
Pressure dew point | 16℃ | 4.8℃ |
Nameplate power | 13.5kW | 8.2kW |
Measured current | 21.8A | 13.5 |
Cooling water flow | 13.5T/h | 7T/h |
Control | On site start stop, employee complaint | Remote, chain, communication |
Performance analysis:
The pressure drop at the inlet and outlet of the whole machine is only about 0.01Mpa, which means that the air compressor can be set with lower exhaust pressure;
Pure countercurrent heat exchange system, air inlet and outlet temperature difference of 10 ℃. The regenerative system recovers 40% more cooling capacity than the traditional shell and tube dryer, which is the fundamental reason for energy saving of plate exchange dryer. Under the same working condition, it can save more than 30% energy and truly achieve "low dew point" and "low energy consumption".
QQ: 89080830
Phone: +86-18080420046
Tel: +86-28-84369018
Email: 89080830
Add: Room 1010, Building 5,No.199,Road Huaishudianlu,City Chengdu,China